Trayer Solid Dielectric Ratings for the Unit/System Voltage |
||||||||
Nominal Voltage (Series) |
15kV |
25kV |
||||||
Maximum Design Voltage |
15.5kV |
27kV |
||||||
Device |
Load Break |
Vacuum Fault |
Load Break |
Vacuum Fault |
||||
BIL Phase-to-Phase, Phase-to-Ground |
110kV |
110kV |
110kV |
110kV |
125kV |
125kV |
125kV |
125kV |
BIL Across Open Contacts |
110kV |
110kV |
110kV |
110kV |
125kV |
125kV |
125kV |
125kV |
One Minute Withstand (60Hz) |
34kV |
34kV |
34kV |
34kV |
40kV |
40kV |
40kV |
40kV |
Continuous Current |
630A |
630A |
630A |
630A |
630A |
630A |
630A |
630A |
Load Switching |
630A |
630A |
630A |
630A |
630A |
630A |
630A |
630A |
Peak Current |
41.6kA |
52kA |
41.6kA |
52kA |
41.6kA |
52kA |
41.6kA |
52kA |
Load Break Operations at Full Load |
10,000 |
10,000 |
10,000 |
8,000 |
10,000 |
10,000 |
8,000 |
8,000 |
Maximum Emergency Three-Time Interrupting |
2000A |
2000A |
N/A |
N/A |
2000A |
2000A |
N/A |
N/A |
Number of Fault Interruptions at 16kA |
N/A |
N/A |
65 |
65 |
N/A |
N/A |
65 |
65 |
Short-time Withstand Current (1s), Short Circuit Current, and Fault-making Current 600A Symmetrical |
16kA |
20kA |
16kA |
20kA |
16kA |
20kA |
16kA |
20kA |
Short-time Withstand Current (1s), Short Circuit Current, and Fault-making Current 600A Asymmetrical |
25.6kA |
32kA |
25.6kA |
32kA |
25.6kA |
32kA |
25.6kA |
32kA |